Training Manual

Single Loop Template Lab

Next, we will change some of the system alarm settings.

1

Press DOWN

DIAGNSTC RATE

is displayed on lines 1 and 2.

FAST = off 100mSec, on 300 mSec.
SLOW = off 250mSec, on 750mSec.
We will accept the FAST rate.

Alarm indication rates apply to light, display
and beeper. Alarms are: unacknowledged
diagnostics, high or low process and deviation
conditions, and input quality

2 Press

NXT

DIAGNSTC FLASH

is OFF.

OFF = flashing is disabled.
ENABLE = flash display (LED always flashes
for diagnostic).

3

Press NXT.

DIAGNSTC BEEP

is OFF

OFF = beeping is disabled.
ENABLE = beep for diagnostic.

4 Press

NXT

5 Set

MINIMUM LOW PRI

to 5 and press ENT.

All process alarms with priority >= this value (2
- 255) are considered LOW priority for display
purposes.

6 Press

NXT

HIGH PRI RATE

is FAST.

FAST = off 100mSec, on 300 mSec
SLOW = off 250mSec, on 750mSec

7 Press

NXT

8 Set

HIGH PRI FLASH

to ENABLE and press

ENT

OFF = flashing is disabled
ENABLE = flash display on alarm

Figure 3 .13.