Single Loop Template Lab

key to set the range at 200. Then press
ENT

Significant Digit to flash, indicating you can
change that digit. Each time you press the FST
key the flash digit will move one digit to the left.
Pressing one of the arrows will cause the flashing
digit to ramp up or down.

12 Press

NXT

EU LABEL

will be displayed on line 2.

Figure 3 .17.

13

Using the UP/DOWN keys and NXT key,
spell out GPM
Then press ENT

Up to a 4 character label to appear after process
input value. First character entered becomes
leftmost character

14 Press

NXT

LO QUAL

is displayed on line 2

15

Using the UP/DOWN keys enter -20.0 as
low quality limit. Then press ENT

Result is set BAD if it goes below this value.

Figure 3 .18.

3 - 18