Training Manual

Single Loop Template Lab

3.3.9 Process Input Setup

1 Press

NXT

PROC INP

will be displayed on line 2. We are

entering the process input setup for our PID
control loop.

2

Press DOWN

This takes you into the process input definition
menus. SLOT will be displayed on line 2.

3

BI 1 AIN

is the default input. We will

accept this.

This is Built-In Analog Input 1. Inputs may be
defined as NONE, BI AIN 1, BI AIN 2 or module
slot S01- to S11- for input being configured

4 Press

NXT

INP TYPE

will be displayed on line 2.

Figure 3 .16.

5

VOLTS

is the default for the process input.

Press UP and then ENT to change this
to CURRENT.

Input types may be defined as: VOLTS, MVOLTS,
CURRENT, RESIST, THRMOCPL
1 Slot: RTD2WIRE, CURRNT2W
2 Slots: RTD3WIRE, WIDERES
Built-in only: TC W/CJC, RTD

6

Press NXT until LO SIGNL is displayed on
Line 2

7

Press the DOWN arrow and FST/SLO
keys to change the low signal range to 4

Built-in analog input 1 is wired to a pot in the
demonstration unit which has a range of 0 to 6
Volts

8 Press

NXT

HI SIGNL

is displayed on line 2

9

Use the UP and FST keys to change the
high signal range to 20 and press ENT

10

Press NXT until HI ENGU is displayed on
line 2

11

Use the UP/DOWN keys and the FST

Pressing the Up key, will cause the Least

3 - 17