Sequence Lab

Figure 12 .17.

SEQ Properties -
Outputs Tab



Another powerful feature of the Sequence Block is that each output can be assigned
names. These names can be used in the step logic expressions. The outputs can be
assigned different values in each step based on the logic. Outputs can be any data type
supported by MOD30ML, including discrete and floating point.

• Add more outputs as per the following table:

Output

Number

Name Type

Initial

Data

2 DrainV Discrete

False

Drain

Valve

3 Setpoint

Floating

Point 0.0 Heating/Cooling

Setpoint

4

CtrlMode

Short State

0

Sends new mode status
to temp controller

5 SetMode Discrete False

Triggers

temp

controller mode change

After adding all the outputs, the Outputs tab should look like the following figure:

12 - 12