2 application #1, 3 application #2, 4 application #3 – Micromod MOD: 30MLTraining Manual User Manual

Page 175

Advertising
background image

Training Manual

Expression Block Lab

11.3.2 Application

#1

Find the average pressure between four boiler headers.

Hints: Add 4 analog input (4-20 mA) and corresponding Signal conditioning blocks. Add
an EX block and configure 4 inputs. Use these 4 inputs in your expression to find the
average.

11.3.3 Application

#2

Turn on a fan when the temperature is greater than 82 degrees and provided the room door
is not open.

Hints: You need a thermocouple or RTD input and a signal conditioning blocks.
Configure a DIM block for the room door and a DOM block for the fan. Use If Then Else
statement or simple mathematical expression in the EX block.

11.3.4 Application

#3

Select the one input out of 4 that is the lowest value.

Hints: Configure 4 inputs. There are more than one ways of configuring this in the EX
block. One of them is to use nested If Then Else statements. Take one input at a time and
compare that with the other 3 inputs to see if it is the lowest.

11 - 3

Advertising
This manual is related to the following products: