CJC and Display Lab

simulated input value.

11.

Close the block with the OK button.

B- CONFIGURE SIGNAL CONDITIONING

Step Procedure

Comments

1.

From the Library window, select a TI block and
place it on the screen near your AIN block.

This block converts the mV to the selected
engineering units (Celsius, Fahrenheit, Rankine or
Kelvin)

2.

Double-click on the TI block

3.

Enter the block name TI-100

We will accept the default configuration for the
block

4.

Close the block



C - PLACE THE DISPLAY BLOCK

Step Procedure

Comments

12.

In the Library window, click on DISP , drag the
box onto the screen and fix it in place

This is the Display block

13.

Double-click on the Display block

14.

Change the block name to TempDisp

This is NOT the tag name that appears on the
display during operation; it is the block reference
name.

15.

Type in the name TI-100 in the Display Tag
field.

This is the tag name we will use to reference the
display in the Display Interface Block, and on the
front of the instrument.

16.

Under Initial display data, type DISPTAG in
the Line 1 field.

This will cause the Display Tag (as entered in the
Display Tag field) to appear on Line 1 of the
display.

17.

Type “TI” in the Line 5 field. DO NOT close
the block.

DOUBLE QUOTES ARE REQUIRED. The text
TI will appear on line 5 of the display after the
download. The quotes indicate text rather than an
input name.

18.

Type TI in the Line 6 field.

DO NOT use quotes! This will be an input name,
and the value will be displayed in Line 6.