12 output setup – Micromod MOD: 30MLTraining Manual User Manual

Page 49

Advertising
background image

Training Manual

Single Loop Template Lab

3.3.12 OUTPUT Setup

1

Press DOWN to enter output section

2

Leave the default value of BI1 AOUT in
place

NONE, BI1 AOUT, BI2 AOUT, and
S01 to S11. Only available outputs are listed.

3 Press

NXT


OUTPUT LO SIGNL

displayed. 0% of the output

range.

4 Press

NXT


OUTPUT HI SIGNL

displayed. 100% of the output

range

Figure 3 .23.

5

Press NXT until OUTPUT LO LIMIT
displayed

PID output limited to this number or above.

6

Set limit to 0.0. Then press ENT

7 Press

NXT,

OUTPUT HI LIMIT

displayed

PID output limited to this number or below.

3 - 23