6-9
6.3
Notes on wiring
6
Wiring
As with single-axis systems, max. cable runs can only be achieved if the
material requirements are strictly observed.
Insulation material
`
Special thermoplastic
][Funktion_Zwischenkreis_Wichtig
NOTICE
High transient currents between connected intermediate circuits
can destroy the servo amplifier. v
- Supply the servo amplifier from the same mains (identical
mains voltage).
- Do not wire servo amplifiers with smaller outputs between two
servo amplifiers with higher outputs.
- Ensure that the total rated currents of all the servo amplifiers
connected in parallel in an intermediate circuit does not exceed
48 A.