3.1
Intended use
3
Safety
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
3-2
nical details”. Ventilation or cooling may be required to maintain the
control cabinet temperature below 40 °C.
][EMV_Wohnumgebung
3.1.4
Guidelines for UL approval
Guidelines for UL approval
3-
][Sicherheit_Bestimmung_UL
Please note the following guidelines for UL approval:
`
Only use copper wiring that can withstand temperatures of 60°/75°C.
`
Only use Class 1 wiring or comparable.
`
Clamping torque for power connection terminals:
X0, X8, X9: 0.7 - 0.8 Nm
`
Only use the servo amplifier in max. pollution degree 2 environments.
`
The servo amplifier can be used on supply networks that are able to
provide no more than 42 kA symmetrical at a maximum voltage of 480
VAC.
Power supply protection:
`
The servo amplifiers may be interconnected in compliance with the
technical details for the DC intermediate circuit. In the power feed the
devices can be protected with a group fuse that complies with the
max. single fuse rating (e.g. 3 x PMCprotego D.01 with a common
6AT fuse).
WARNING!
In a residential environment this product may cause high-fre-
quency noise, so that suppression measures may be required.
Device
Fuse class
Nominal data
Max. fuse rating
PMCprotego
D.01
RK5, CC, J, T
600 VAC 200 kA
6 A (Time delay)
PMCprotego
D.03
RK5, CC, J, T
600 VAC 200 kA
6 A (Time delay)
PMCprotego
D.06
RK5, CC, J, T
600 VAC 200 kA
10 A (Time delay)
PMCprotego
D.12
PMCprotego
D.12 P
RK5, CC, J, T
600 VAC 200 kA
15 A (Time delay)
PMCprotego
D.24
PMCprotego
D.24 P
RK5, CC, J, T
600 VAC 200 kA
30 A (Time delay)