Switch on/switch off behaviour

4

Function Description

4.5

Switch on/switch off behaviour

4500

Switch on/switch off behaviour

4-

][Funktion_Ein_Aus_Allg

This section describes the behaviour of the servo amplifier when switch-

ing on and off. It explains the measures that are required to achieve

compliance with the standards when a stop or E-STOP is performed

during operation.

*) please refer also to the ASCII object reference in the commissioning

software's online help

Behaviour during a power failure

The servo amplifier detects the failure of one or more input phases.

The behaviour of the servo amplifier is set using the commissioning soft-

ware: In the “Basic Setup” window, under “Response to Loss of Input

Phase”, select (PMODE):

`

A warning appears if the higher level control system is intended to

bring the drive to a standstill:

A message indicates that an input phase is missing (message “n05”)

and the motor current is limited to 4 A. The servo amplifier is not

switched off. The higher level control system can now either end the

current cycle specifically or bring the drive to a standstill. The error

message “NETZ-BTB, F16”, for example, is sent to a digital output on

the servo amplifier and is evaluated by the control system.

`

An error message appears if the servo amplifier is intended to bring

the drive to a standstill:

A missing input phase is registered as an error (error message “F-

19”). The servo amplifier is switched off; the BTB relay contact for op-

erational readiness opens. If the factory default setting is unchanged

INFORMATION

The servo amplifier's 24 VDC supply must be maintained even

after a stop or emergency stop.

The parameters ACTFAULT (reaction to fault) and STOPMODE

(reaction to ENABLE signal) define how the drive behaves when

it is switched off.

ACTFAULT/STOPMODE

Behaviour*

0

Motor runs down in an uncontrolled
manner

1 (default)

Motor is braked in a controlled man-
ner

Advertising
This manual is related to the following products:

PMCprimo DriveP.01/AA0/5/0/0/208-480VAC, PMCprimo DriveP.12/AA0/4/0/0/208-480VAC, PMCprimo DriveP.12/AA0/4/P/0/208-480VAC, PMCprimo DriveP.03/AA0/4/0/0/208-480VAC, PMCprimo DriveP.06/AA0/4/0/0/208-480VAC, PMCprimo DriveP.24/ABB/4/0/0/208-480VAC, PMCprimo DriveP.03/AB0/5/0/0/208-480VAC, PMCprimo DriveP.06/AB0/2/0/0/208-480VAC, PMCprimo DriveP.03/AB0/3/0/0/208-480VAC, PMCprimo DriveP.06/AB0/3/0/0/208-480VAC, PMCprimo DriveP.12/AB0/2/0/0/208-480VAC, PMCprimo DriveP.12/ABC/4/P/0/208-480VAC, PMCprimo DriveP.12/AB0/3/0/0/208-480VAC, PMCprimo DriveP.03/AB0/2/0/0/208-480VAC, PMCprimo DriveP.12/AAC/4/0/0/208-480VAC, PMCprimo DriveP.24/AA0/5/0/0/208-480VAC, PMCprimo DriveP.12/AA0/2/0/0/208-480VAC, PMCprotego D.01/000/0/0/2/208-480VAC, PMCprotego D.03/000/0/0/2/208-480VAC, PMCprotego D.06/000/0/0/2/208-480VAC, PMCprotego D.12/000/0/0/2/208-480VAC, PMCprotego D.24/000/0/0/2/208-480VAC, PMCprotego D.12/000/0/P/2/208-480VAC, PMCprotego D.24/000/0/P/2/208-480VAC, PMCprotego D.01/200/0/0/2/208-480VAC, PMCprotego D.01/100/0/0/2/208-480VAC, PMCprotego D.01/010/0/0/2/208-480VAC, PMCprotego D.06/010/0/0/2/208-480VAC, PMCprotego D.06/100/0/0/2/208-480VAC, PMCprotego D.06/200/0/0/2/208-480VAC, PMCprotego D.03/010/0/0/2/208-480VAC, PMCprotego D.03/200/0/0/2/208-480VAC, PMCprotego D.03/100/0/0/2/208-480VAC, PMCprotego D.12/010/0/0/2/208-480VAC, PMCprotego D.24/200/0/P/2/208-480VAC, PMCprotego D.12/200/0/0/2/208-480VAC, PMCprotego D.12/100/0/0/2/208-480VAC, PMCprotego D.12/010/0/P/2/208-480VAC, PMCprotego D.12/200/0/P/2/208-480VAC, PMCprotego D.24/100/0/P/2/208-480VAC, PMCprotego D.24/010/0/P/2/208-480VAC, PMCprotego D.12/100/0/P/2/208-480VAC, PMCprotego D.24/200/0/0/2/208-480VAC, PMCprotego D.24/100/0/0/2/208-480VAC, PMCprotego D.24/010/0/0/2/208-480VAC