25 modbus/snmp/bacnet slave units, Modbus/snmp/bacnet slave units – RLE FMS V.1.13 User Manual

Page 104

Advertising
background image

104

FMS User Guide

800.518.1519

3

Web Interface Configuration

3.4.25 Modbus/SNMP/BACnet Slave Units

This section provides configuration information for basic Slave unit functionality. If you’d

like to configure more advanced features, including Modbus Register Configuration, refer to

Chapter 4, “Advanced Communications - Modbus, BACnet, and Telnet” on page 133

.

The Modbus/SNMP Slave Unit Configuration can only be configured after the Modbus/

SNMP/BACnet/Telnet Master has been set up; see

“Modbus/SNMP/BACnet/Telnet Master”

on page 101

. Users must tell the FMS that they are using it for Modbus communications

before users can configure the Modbus slave units.

The Slave Unit Configuration page will change depending on what type of Protocol users set it

up for (i.e., Modbus/SNMP/BACnet Master - 32 Units, Modbus Master BCM H663 - 4 Units,

or Modbus Master BCM H663 - 16 Units). This option is selected on the Modbus/SNMP/

BACnet/Telnet Communication page; see

Figure 3.26 on page 78

.

If you’re configuring a Branch Circuit Monitor, refer to

“Modbus/Slave Units Configuration –

Modbus Master Branch Circuit Monitor– 4 or 16” on page 152

.

If you’d like to

Most frequently, the FMS will be configured for Modbus/SNMP/BACnet Master - 32 Units,

and the following page will display. Use this page to configure the information regarding the

Modbus Slave devices from which the FMS will poll.

Figure 3.40

Modbus/Snmp/BACnet Slave Unit Configuration Page

Advertising