Advanced Communications - Modbus, BACnet, and Telnet

4.8. Telnet

The FMS supports a Telnet connection over IP port 23. When properly configured a Telnet

user can use the Com1 port of the FMS to communicate to external EIA-232 enabled devices.

4.8.1 Hardware Connections

The Com1 port is located on the back of the FMS. The COM1 Transmit and Receive LEDs are

also located on the back of the FMS.

The EIA-232 port allows communications between the FMS and one other device (point-to-

point connection). The EIA-232 port has maximum cable length of 50 feet (15.2m).

Figure 4.19

FMS Connection to an EIA-232 Device

Connect a nine-pin, straight-through serial cable to the FMS and to the other device.

Once you connect the serial cable, the FMS automatically switches to EIA-232 mode.

Pin

Description

Pin 1

Data Carrier Detect

Pin 2

Receive Data

Pin 3

Transmit Data

Pin 4

Data Terminal Ready

Pin 5

Signal Ground

Pin 6

No Connection

Pin 7

Request to Send (internally connected to Pin 8)

Pin 8

Clear to Send (internally connected to Pin 7)

Pin 9

No Connection

Table 4.13

COM1 DB9 Male Pin Out