Technical Specifications

Expansion Cards

EXP-A-24 or EXP-A-48

1U accommodates 1 expansion card; 2U accommodates up

to 4 expansion cards
24V Falcon requires EXP-x-24 option cards; 48V Falcon

requires EXP-x-48 option cards
12 analog inputs (jumper selectable for 4-20mA, 0-5VDC or

0-10VDC) and digital inputs (non-isolated, individual ground

only);

8 Form C Relay Outputs, 1A @ 24VDC, 0.5A resistive @

120VAC

EXP-C-24 or EXP-C-48

24 Digital Inputs, 3000VAC RMS optically isolated (common

ground or individual ground)

Communications Ports

Ethernet

10/100BaseT, RJ45 connector; 500VAC RMS isolation

EIA-232

DB9 female connector; 9600 baud; 3000VAC RMS optically

isolated; 15kV ESD protection

EIA-485 (selectable as EIA-232)

Two-wire half duplex; terminal block (selecting EIA-232

switches to DB9 male connector); 1200, 2400, or 9600 baud

configurable; 3000VAC RMS optically isolated

Modem (RJ11 Telco) – Optional

V.34bis/33.6 kbps; DTMF capable; PPP-Enabled; FCC Part

68 approved; 1500VAC RMS isolation barrier; 2100V peak

surge protection

Protocols

TCP/IP, UDP/IP, ICMP/IP, FTP,

NTP

IPv4

HTTP/HTML, SNPP, Telnet

1.1/4.0; up to 10 URL links to other IP addressable

cameras/devices; webpages comply with Rehabilitation Act

of 1973, sections 504 and 508, US Dept of Education

(website accessibility for computer users with disabilities)

SNMP

V1: MIB-2 compliant; NMS Manageable with Get, Set, and

Traps; V2c: Traps or Informs; V3 (optional)

SMTP (Email)

Supports Client Authentication (plain and login); compatible

with ESMTP Servers

Modbus

RTU transmission protocol; function codes: Slave - 03;

Master - 01,02,03,04

Modus/IP

Modbus Slave; TCP/IP transmission protocol

BACnet/IP

Reads up to 106 instances and converts to SNMP and

Modbus

Terminal Emulation

VT100 compatible

TAP (Pager)

Telocator Alphanumeric Protocol Ver1.8

Table J.1

Technical Specifications (continued)