1 designating pue/dcie data, Designating pue/dcie data – RLE FMS V.1.13 User Manual

Page 109

Advertising
background image

rletech.com

FMS User Guide

109

3

Web Interface Configuration

3.4.26.1 Designating PUE/DCiE Data

1

Before you can generate the PUE/DCiE data, you need to know where to tell the FMS to

find the raw kW readings. The Modbus registers for this information should already be

configured. On the FMS interface, go to Configuration > Modbus/SNMP Slave Units.

2

Click the appropriate link to access the range of Registers where your devices are located.

Write down the index numbers of the kW-related Modbus registers. You’ll need to enter

these index numbers on the PUE/DCiE Configuration page.

Figure 3.44

Gather Modbus Register Information

3

On the FMS interface, return to the to Configuration>PUE/DCiE/Summary/Average

screen.

4

At the top of the PUE/DCiE/Summary/Average Configuration page, you’ll see a drop down

menu to enable or disable the PUE/DCiE feature. Select an option as follows to begin the

setup:

DC1 - generate one PUE/DCiE value

DC2 - generate two PUE/DCiE values

DC1+2 - generate two PUE/DCiE values and a summary and/or average of those values

5

You can view PUE/DCiE information on the main FMS page in two ways - either as

statistics, or as statistics and a gauge. The FMS can generate a Java-based gauge graphic on

its home page that allows you to see a graphical representation of either your PUE or your

DCiE value. If you’d like to display this gauge, select either PUE or DCiE from the drop

down menu next to the PUE/DCiE Gauge field. If you leave this setting disabled, only

statistics will display on the FMS home page.

Figure 3.45

Enable PUE/DCiE and Designate Gauge Behavior

Modbus Registers - kW Data

Advertising