1 cb# links, Cb# links, Table 4.9 – RLE FMS V.1.13 User Manual

Page 154: Circuit breaker configurations for individual bcms

Advertising
background image

154

FMS User Guide

970.484.6510

4

Advanced Communications - Modbus, BACnet, and Telnet

4.6.1.1 CB# Links

Pressing a CB # (CH#) link displays the Circuit Breaker Configurations for each BCM.

Figure 4.18

Circuit Breaker Configurations for Individual BCMs

Option

Description

Label

Enter a label to describe the circuit breaker. The label is included in

notifications and for identification on the Slave Unit Monitoring

page.

Zero Amp Enable

Check to enable alarm and notification if the branch circuit current

falls below the zero amp level as set on the Slave Configuration

page.

Breaker Size

Enter the circuit breaker size in the BCM.

Warning Threshold

Enter the warning threshold level-in percent-in the BCM.

Alarm Threshold

Enter the alarm threshold level-in percent-in the BCM.

Warning Time Delay

Enter the warning time delay-in seconds-in the BCM.

Alarm Time Delay

Enter the alarm time delay-in seconds-in the BCM.

Table 4.9

Circuit Breaker Configurations for Individual BCMs