Configuration, 1 inputs and relays, Inputs and relays – RLE FMS V.1.13 User Manual

Page 43: Figure 3.4

Advertising
background image

rletech.com

FMS User Guide

43

3

Web Interface Configuration

3.4. Configuration

The Configuration page allows authorized users with administrator or read-write privileges to

adjust the FMS settings. Each link on the Configuration page displays more information about

specific configuration settings.

Figure 3.4

Configuration Page

NOTE: If any of the fields within the sub-menus are edited, be sure to click the Submit

Changes button to save the changes. If you edit the fields and navigate from the web

pages without clicking the Submit Changes button, all changes will be lost.

3.4.1 Inputs and Relays

Inputs and Relays allows users to program specific parameters for each FMS input and relay.

Only installed inputs and relays are displayed.

Different FMS models allow different numbers of inputs and relays. A1U will include the

Main Board inputs, and has room for one expansion card - either an A card or a C card.

A 2U FMS allows 4 expansion cards to be added to the unit - each expansion card slot can be

outfitted with either an A card or a C card.

Main Board Inputs 1-8 - Every FMS has a main board. This board provides 8 inputs

configurable as analog 4-20mA or digital NO/NC.

Expansion Card A Inputs and Outputs- adds an additional 12 inputs, configurable as analog

4-20mA, 0-5V, 0-10V or digital NO (cannot be configured as NC), as well as 8 form C

relay outputs.

Expansion Card C Inputs - adds an additional 24 digital NO/NC inputs. There are no

additional relay outputs on a C card