2 pue/dcie trending, Pue/dcie trending, Figure 3.47 data for third party applications – RLE FMS V.1.13 User Manual

Page 111: Format trends

Advertising
background image

rletech.com

FMS User Guide

111

3

Web Interface Configuration

9

Information has also populated at the bottom of the chart. Use this information if you wish

to output the PUE/DCiE information to a third party application or generate PUE/DCiE

trending information. Modbus, BACnet, and SNMP output information is provided.

Figure 3.47

Data for Third Party Applications

3.4.26.2 PUE/DCiE Trending

Now that the FMS is generating PUE/DCiE information, it can log long-term trending data.

The trending program can log 3840 entries. Once 3840 entries have been logged, the system

will eliminate 40 entries at a time and overwrite the data, from oldest to newest. Long-term

trending is the most effective way to use PUE/DCiE data.

Format Trends

1

On the FMS interface, go to Configuration>Trends.

2

You may already have some trending tasks operating on the FMS. Select the next available

index number. Use the following points to trend your data:

3

Select Modbus/SNMP as the type.

4

Now, determine the interval at which you wish to trend the data. The interval is selectable,

from a 1 minute interval to an 8 hour interval - it just depends how detailed you’d like your

data to be. At a 1 minute interval, the FMS will store approximately 2.5 days worth of data

Point Value

Trended Data

629

DCiE 1

630

PUE 1

631

DCiE 2

632

PUE 2

633

DCiE 1 + 2

634

PUE 1 + 2

635

Summary 1

636

Summary 2