6 trends, Trends, Table 3.8 – RLE FMS V.1.13 User Manual

Page 67: Trend interval chart

Advertising
background image

rletech.com

FMS User Guide

67

3

Web Interface Configuration

3.4.6 Trends

This feature allows users to configure custom trending on an analog point, either physical or

Modbus.

Figure 3.15

Trends Configuration Page

Data can be trended for 8 or 32 points. If you choose to trend 8 points, the FMS will trend

16128 entries per point. If you choose to trend 32 points, the The FMS compiles 3840 entries

per point. Once the maximum number of entries has been reached, the FMS eliminates 40

entries at a time and overwrites the data, from oldest to newest. You determine the time

interval for the data collection, depending on how detailed you’d like the information.

Time intervals range from 1 minute to 8 hours, and total sample collection is as follows:

Figure 3.16

Trend Configuration Menu Options

Interval

Samples per

Day

Total Days

Interval

Samples per

Day

Total Days

1 minute

1440

2.6

2 hours

12

320

5 minutes

288

13.3

4 hours

6

640

15 minutes

96

40

6 hours

4

960

1 hour

24

160

8 hours

3

1280

Table 3.8

Trend Interval Chart

Option

Description

Point

The physical channel or Modbus index number.

Type

Select either Physical or Modbus SNMP.

Interval

Select the Interval you’d like to use for trending.

Info

Uneditable field.

Format

Once all your information has been filled out, click this button.