Analog 4-20Ma Gain/Offset Conversion Formula:

Gain = Sensor Range (High Value - Low Value) / 4

Offset = Sensor Low Value - Gain

Example: TH140 Humidity

Gain = (High Value (100) -Low Value (0)) / 4 = 25

Offset = (Sensor Low Value (0) - Gain (25)) = -25

RLE

Product #

Transducer Type

Range

Gain

Offset

TEMPERATURE

TH140

Temperature (Display in Deg F)

32°F - 120°F

22

10

Temperature (Display in Deg C)

0°C - 48.8°C

12.2

-12.2

Humidity

0% - 100% RH

25

-25

T120

Temperature (Display in Deg F)

32°F - 122°F

22

10

Temperature (Display in Deg C)

0°C - 48.8°C

12.2

-12.2

CURRENT

CT55

Current

0 - 5 Amps

1

-1

0 - 55 Amps

13

-13

CT20

Current

0 - 30 Amps

7

-7

0 - 60 Amps

15

-15

0 - 120 Amps

30

-30

CT200

Current

0 - 20 Amps

5

-5

0 - 200 Amps

50

-50

Table C.1

Analog Input 4-20mA Reference Chart