Figure a.8, Figure a.9 – RLE FMS V.1.13 User Manual

Page 185

Advertising
background image

rletech.com

FMS User Guide

185

A

FMS Expansion Cards

A.3.

Convert Current Input Channels to Voltage Input

Channels on Expansion Card A

When the FMS optional 12 channel analog input card is delivered, its channels are configured

for current inputs (4-20mA). Some sensors, however, may require voltage input channels (0-

5V or 0-10V). The customer may manually reconfigure any or all current input channels as

voltage input channels if necessary.

The headers on the expansion card are labeled P1 through P12. Each number corresponds with

a channel (e.g., P1 corresponds with channel 1, while P10 with channel 10.) Each header has

two parallel columns of five pins. Some pins are connected with jumpers. Changing these

header settings converts a current channel to a voltage channel, and vice versa.

To configure a header as a current channel (4-20mA), connect pins 1 and 3 with one jumper.

Connect pins 2 and 4 with another jumper. Connect pins 7 and 8 with a third jumper.

Figure A.8

Expansion Card Current Channel (4-20mA) Configuration

Note Expansion cards are shopped from the factory with all headers configured as current

channels.

To configure a header as a voltage channel (0-5V or 0-10V), connect pins 3 and 5 with one

jumper. Connect pins 4 and 6 with another jumper. Connect pins 9 and 10 with a third jumper.

Figure A.9

Expansion Card Voltage Channel (0-5V or 0-10V) Configuration

Advertising