134

FMS User Guide

970.484.6510

4

Advanced Communications - Modbus, BACnet, and Telnet

4.2.1 EIA-232

The EIA-232 COM Port 1 on the FMS is used to connect the FMS-as a Modbus Master-to one

Modbus Slave device, or it is used to connect a Modbus Master device to the FMS as a

Modbus Slave. The Modbus EIA-232 (DTE) is active over COM1 (DB9 male connector). The

EIA-232 port allows communications between the FMS and one other device (point to point

connection). The EIA-232 port has maximum cable length of 50 feet (15.2m).

Figure 4.1

FMS Modbus EIA-232 Connection to an EIA-232 DCE Device

Pin

Description

1

Data Carrier Detect

2

Receive Data

3

Transmit Data

4

Data Terminal Ready

5

Signal Ground

6

No Connection

7

Request to Send (internally connected to Pin 8)

8

Clear to Send (internally connected to Pin 7)

9

No Connection

Table 4.1

COM1 DB9 Male Pin Out