Table 3.28, Modbus/snmp/bacnet slave configuration options – RLE FMS V.1.13 User Manual

Page 105

Advertising
background image

rletech.com

FMS User Guide

105

3

Web Interface Configuration

The numbers in the Unit # column are links. Click the links to configure the individual slave

devices.

Figure 3.41

Modbus/SNMP/BACnet Slave Configuration Page

Option

Description

Communications

Configure the FMS to send Modbus requests to a specific slave

device over either a serial connection (EIA-232 or EIA-485) or over

TCP/IP. This configuration can be different for each slave unit.

TCP/UDP/IP IP

Address

Enter the IP address of the slave unit here.

Protocol

This option allows the FMS to send appropriate requests to each

slave device. Refer to the documentation of the slave device for

proper configuration.

The FMS supports the following communications protocols:

Modbus Standard

Modbus Extended

JBus

SNMP V1

SNMP V2

BACnet/IP

BACnet Destination

Network

If the device is on another network, specify the destination network

here.

Table 3.28

Modbus/SNMP/BACnet Slave Configuration Options