RLE FMS V.1.13 User Manual

Page 148

Advertising
background image

148

FMS User Guide

970.484.6510

4

Advanced Communications - Modbus, BACnet, and Telnet

Object Type

Select the appropriate object type:

Long Integer (32 bits)

Float (Converted Display String)

Scaler

Select a multiplier for the data value.

Custom Gain

If you’d like a gain to be applied to the value, designate that here.

Offset

Allows users to fine-tune analog values. Offset adjustment may be

required by certain manufacturers.

Label

Enter a label to describe the Data Point.

UOM/Map Label

Specify the unit of measure you are using for this specific point.

Log Index

Applies to Data Types Signed Int, Unsigned Int, Long and Float.

The FMS has 232 entries reserved for logging (Min, Hour and Day

Logs). Enter a value of 1 to 232 if the point is to be internally logged

on the FMS. Each register to be logged requires a unique entry

number.

UOM Conversion

Convert a unit of measure from the way it is communicated by the

device to the way you would like to have it displayed.

deg C - deg F (1,10,100,1000 Scale)

deg C - deg F (1/32 Scale

kPa - PSI (1/8, 1/28 Scale)

Enumerated Label

Set

Sets of enumerated labels can be configured from the Enumerated

Labels Configuration link on the bottom of the Modbus/Snmp/

Bacnet Slave units page. If you have a label set configured,

designate which one you’d like to use here.

Alarm Type

Designate which type of alarm this will be.

Alarm Thresholds:

High 2, High1, Low1,

Low2

Set high and low - or major and minor - thresholds for alarm analog

alarm values being read by these points.

Enumerated Active

Value

If you’d like to designate an enumerated active value, do so here.

Snmp Trap

Recipients

The SNMP/Syslog page allows you to configure SNMP trap

recipients. Once those are configured, you can designate which IP

addresses should receive traps for this register.

Map Box Size

Customize the size of the mapped object. By default, the height of

the object, as it appears on the map, is approximately 20 pixels,

and the width automatically adjusts to the length of the text. This

setting allows users to expand the size of the object to fill a defined

area.

Map Coordinate

Fine tune the location of the object on the map. Refer to

“Map

(Facility Mapping)” on page 114

for further information.

Graphical Mapping

Designate the device’s location on the FMS graphical map. Refer to

“Map (Facility Mapping)” on page 114

for further information.

Test Map

View the mapped location of the point you’re currently configuring.

Option

Description

Table 4.7

Individual Snmp Register Configuration Options