Web Interface Configuration

Low Limit1 (Minor)

Applies only to analog 4-20mA inputs.

The FMS will record an alarm and send notification when the FMS

calculated value falls below this limit. The Low Limit 1 and Low

Limit 2 are disabled when they are both set to 0.

Low Limit2 (Major)

Applies only to analog 4-20mA inputs.

The FMS will record an alarm and send notification when the FMS

calculated value falls below this limit. The Low Limit 1 and Low

Limit 2 are disabled when they are both set to 0. Low Limit 2 will

also activate any designated relays.

Pager Alarms

Use the Configuration>Modem/Phone Numbers/Pagers link to

configure alarm recipients. You can configure up to 15 phone

numbers, and each will go into a numbered slot, 1 - 15.

Then come back to this field and designate up to five recipients who

should be notified when this point goes into alarm. Separate the

recipients’ ID numbers with commas. The FMS will first dial the

lowest number listed, regardless of the order in which the numbers

are listed.

Enter zero to disable this feature.

Example: If the Alarm dial out string is set to “3, 5, 1, 0, 0,” the FMS

will dial Pager #1, Pager #3 and then Pager #5 when an alarm

occurs. Pager notification will be sent when an input alarms (high

limit 2, high limit 1, low limit 1, low limit 2 is exceeded or the digital

input is in alarm). See

3.4.13, “Modem/Phone Numbers/Pagers” on

page 78

for more information.

Label

Enter a unique name for this input.
Applies to all input types except “Not Configured.”

For Analog input types, this label is displayed on the FMS Main

Menu and the Input Configuration Menu. When the input

alarms and/or returns to normal, the label is included in the

Alarm History and notification messages.

For Digital NO and Digital NC inputs, the label is displayed on

the FMS Main Menu, Input Configuration Menu, Alarm History

page and in notification messages only when the device is in

alarm.

For Digital Status inputs, the label is displayed on the FMS

Main Menu when the input is on. When the input turns on, the

label is also included in the Digital Status History.