Figure 2.1, 24vdc power supply connection, Figure 2.2 – RLE FMS V.1.13 User Manual

Page 24: 48vdc power supply connection

Advertising
background image

24

FMS User Guide

800.518.1519

2

Getting Started

recommends powering the FMS from a UPS supply to allow the FMS to send alarm

notification during a power outage.

Figure 2.1

24VDC Power Supply Connection

If you are installing a 48VDC FMS, the FMS must be connected to either:

a

An external 48VDC supply that can be unplugged or switched off.

b

The 48VDC supply bus via a switch or a circuit breaker. The switch or circuit breaker

must be suitable located and easily reached. It must be clearly marked as the

disconnecting device for the FMS.

For a 48VDC model FMS, connect a 48VDC supply through a circuit breaker to TB1 as

shown below. In telecommunications applications, the 48VDC supply is typically connected

to the 48VDC battery system through a DC distribution panel.

Figure 2.2

48VDC Power Supply Connection