Import modbus information to a physical point, Figure 4.8, Input and relay configuration menu – RLE FMS V.1.13 User Manual

Page 142

Advertising
background image

142

FMS User Guide

970.484.6510

4

Advanced Communications - Modbus, BACnet, and Telnet

4.4.

Import Modbus Information to a Physical Point

From the Configuration Menu, click on the Inputs and Relays link. Select any input not

currently in use.

Figure 4.8

Input and Relay Configuration Menu

1

To indicate the input will be pulling in Modbus information, change the Select Input Type

drop down menu from Physical to Modbus Import.

2

Click the Submit Changes button.

3

Once this has been configured as a Modbus Import, the physical channel is no longer

available for additional equipment.

4

Once Modbus Import has been submitted, a new field will appear called Register/Instance

Index. Enter the register index number on the register screen for the selected function.

5

Edit the other fields as necessary. Descriptions of the fields on the Input Configuration

screen can be found on

“Inputs and Relays” on page 43

.