Series 9130 Operations Manual Rev -

101

Temperature Value Column

Atmosphere Value Column

Option Value Column


SET_GEN_FLOW
Multiplier (optional)

Air/Gas Ratio (optional) Total Endo Flow

This opcode will set the flow rate.
The Multiplier is the multiplier for the flow. The range is -3.01 (disable) – 3.20.
The Air/Gas Ratio is the ratio for the air and gas. The range is -0.01 (disable) – 0.10.
The Total Endo Flow is the total flow rate. The range is 0 – 32000.

SET_SL_VAL
Value

Register

Instrument

This option will send a value from a register to a specific instrument.
The Value is the value to send. The range is -32768 – 32767.
The Register is the register to send to. The range is 0 – 32767.
The Instrument is the slave instrument to send the value to. The options are: 1 – 25.

SET_WAIT
Temperature Setpoint N/A

Speed

This opcode sets the band limits for the wait option or inquiry opcodes.
The Temperature Setpoint specifies the temperature band (i.e. +/- the value). The range is -301 (disable) –
30000.
The Speed is the speed to use: Ctrl + Load (T/C), Control (T/C), or Load (T/C).

SETPT
Temperature Setpoint N/A

Option

This opcode is used to set the temperature set point.
The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301
(disable) – 30000.
The Option will wait for the setpoints to be reached: Blank (Don’t Wait), Wait, Wait Up, or Wait Down.

Note –

The Blank option is an actual blank line, not the word “Blank”

.


SL_PV_INQ
Process Variable

Slave

Option

This opcode will check a slave instrument for a specific process variable value, and wait until the PV from
the slave instrument matches.
The Process Variable is the PV to check. The range is -301 (disable) – 32000.
The Slave is the slave instrument to check. The range is 1 – 12.
The Option is the wait options for the opcode. The options are: Wait, Wait Up, or Wait Down.

SOAK
N/A

N/A

Soak Time

This opcode is an unconditional soak for the time (in hours and minutes) specified. The programmer will
hold for the time specified, and nothing except the operator pausing the recipe will put the program in a
hold state.
The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –
166, and the Minutes range from 0 – 59.