Series 9130 Operations Manual Rev -

104

Wait


When using the option wait with a set point Opcode, the recipe will not advance to the next step until the PV
value falls within the wait limit band. The upper limit of this band is value of the PV set point plus the wait
limit. The lower limit of this band is the value of the PV set point minus the wait limi. The wait limit band is
the range between the upper limit and the lower limit. The recipe will then continue to the next step.

For example, assume the PV is temperature with a 1500° set point and a wait limit of 15°. Using the SETPT
opcode, if the option is wait, the recipe will not advance until the temperature PV is 1485°-1515°.