Super Systems 9130 Series User Manual

Page 103

Advertising
background image

Series 9130 Operations Manual Rev -

102

Temperature Value Column

Atmosphere Value Column

Option Value Column


TC_CHK

Source 1

Source 2

Source 3

This opcode will check a TC.
Source 1 will determine the first source to check. The options are: Not Used, Instrument 1 – Instrument 25,
and Input 1 – Input 3.
Source 2 will determine the second source to check. The options are: Not Used, Instrument 1 – Instrument
25, and Input 1 – Input 3.
Source 3 will determine the third source to check. The options are: Not Used, Instrument 1 – Instrument
25, and Input 1 – Input 3.

TC_INQ
Temperature Level

N/A

Option

The temperature inquiry is used to wait for the actual control temperature to reach the value specified.
The Temperature Level is the specified level to wait for. The range is -301 (disable) – 30000.
The Option is the wait options: Wait, Wait Up, or Wait Down.
The default band can be set under the Configuration Menu and is typically 15 degrees. The band limit can
be changed by the S

ET_WAIT

opcode.

The

LIMIT

opcode immediately following this opcode sets a time limit on the wait.

A

BRANCH

opcode immediately following this opcode can be used to change the program flow based on

the inquiry results.

TIME_EVT
N/A

Delay Time

Option

This opcode will turn ON or OFF a specified event for the specified amount of time.
The Delay Time is the time in seconds. The range is: 0 – 500.
The Option is the event to turn ON or OFF. The options are: Event 0 ON or OFF – Event 47 ON or OFF.

TOD_INQ
N/A

N/A

Time

This opcode is a time of day inquiry that would be used to start a process or subroutine at a specific hour
and minute.
The Time is the time to check, in Hours:Minutes format. The Hours range from 0 – 23, and the Minutes
range from 0 – 59.

TZ_INQ
Temperature Level

N/A

Option

The zone temperature inquiry is used to wait for the actual control zone temperature to reach the value
specified.
The Temperature Level is the specified level to wait for. The range is -301 (disable) – 30000.
The Option is the wait options: Wait, Wait Up, or Wait Down.
The default band can be set under the Configuration Menu and is typically 15 degrees. The band limit can
be changed by the S

ET_WAIT

opcode.

The

LIMIT

opcode immediately following this opcode sets a time limit on the wait. A

BRANCH

opcode

immediately following this opcode can be used to change the program flow based on the inquiry results.
This opcode is identical to the

TC_INQ

opcode, except that it will deal with zones.






Advertising