Super Systems 9130 Series User Manual

Page 97

Advertising
background image

Series 9130 Operations Manual Rev -

96

Temperature Value Column

Atmosphere Value Column

Option Value Column

GZ_SOAK
N/A

N/A

Soak Time

This is a guaranteed soak opcode for a zone. The temperature process value must be within the deviation
band to allow the soak timer to run. If the temperature process value goes out of the deviation band, then
the soak timer will stop and wait until the temperature process value comes back into the deviation band
before starting up again.
The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –
166, and the Minutes range from 0 – 59.
The band limit can be changed by the

SET_WAIT

opcode.

GZDELAY
N/A

N/A

Delay Time

This is a guaranteed short delay opcode for a zone. The temperature process value must be within the
deviation band to allow the delay timer to run. If the temperature process value goes out of the deviation
band, then the soak timer will stop and wait until the temperature process value comes back into the
deviation band before starting up again.
The Delay Time is from 1 – 500 seconds.

GZRAMP
Temperature Setpoint N/A

Time

This is a guaranteed ramp opcode for a zone. The process value must be within the deviation band to allow
the ramp timer to run. If the temperature process value goes out of the deviation band, then the ramp
timer will stop and wait until the temperature process value comes back into the deviation band before
starting up again.
The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301
(disable) – 30000.
The Time is the total time for the program to reach the desired setpoint(s), in Hours:Minutes format. The
Hours range from 0 – 166, and the Minutes range from 0 – 59.
The band limit can be changed by the

SET_WAIT

opcode.


HIGH_AL
Temperature Setpoint N/A

N/A

This opcode is used to enable a high limit alarm on the temperature process. This alarm remains active
until the program ends.
The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301
(disable) – 30000.

HIGH_PO
Temperature PO Value N/A

N/A

This opcode is used to enable a high limit alarm on the temperature percent output. The temperature data
is the high limit point for the temperature percent output.
The Temperature PO Value is the high limit point for the temperature percent output. The range is -101
(disable) – 100.
This alarm remains active until the program ends.

ID_INC
N/A

N/A

N/A

This opcode increments the integer ID number by one.

Advertising