Super Systems 9130 Series User Manual

Page 35

Advertising
background image

Series 9130 Operations Manual Rev -

34

Cascade Inhibit

Note: This field is only applicable if the controller is in Cascade mode

. This will turn cascade control on or

off. When inhibit = enabled, the 9130 functions as a multi-loop controller with three control loops. The
options are: enabled or disabled.

PV Difference Cutback

Note: This field is only applicable if the controller is in Cascade Mode

. This is used with the Cascade Lower

Range EOPV and Cascade Upper Range EOPV to limit the absolute % output of the furnace loop. This will
turn the PV difference cutback feature on or off. The options are: enabled or disabled.

Cascade Lower Range EOPV

Note: This field is only applicable if the controller is in Cascade Mode

. This is the cascade lower range end

of PV difference. This is used with the PV Difference Cutback and Cascade Upper Range EOPV to limit the
absolute % output of the furnace loop. Between the lower range EPOV and the upper range EOPV, there is
a linear interpolation from 0 to the loop 2 output maximum (usually 100 %) that determines the maximum %
output for the furnace loop. The range is -300 to 10000.

Cascade Upper Range EOPV

Note: This field is only applicable if the controller is in Cascade Mode

. This is the cascade upper range end

of PV difference. This is used with the Cascade Lower Range EOPV and PV Difference Cutback to limit the
absolute % output of the furnace loop. Between the lower range EPOV and the upper range EOPV, there is
a linear interpolation from 0 to the loop 2 output maximum (usually 100 %) that determines the maximum %
output for the furnace loop. The range is -300 to 10000.

Example: With the Lower EOPV set to 10 and the Upper EOPV set to 110, if the load PV is 1700 and the
furnace PV is 1710, the full 100% output is available. If the load PV is 1600 and the furnace PV is 1710, the
furnace output will not go above 0%. If the load PV is 1655 and the furnace PV is 1710, the maximum output
for the furnace loop will be limited to 55%: (1710 – 1655)/(110-10) * (1.0).

Default Hold Time
This value is the default holding time for the furnace. The range is 0 to 10000.

Deviation Alarm delay
This value is the delay for the alarm if a deviation alarm is detected. The range is 0 to 10000.

Furnace Name
This will allow the user to give the controller a display name.

PV1 Name
This will allow the user to give the first process variable (Temperature) a display name.

Clear events/end of recipe
This switch will allow the user to clear the events out at the end of a recipe. The options are either no or
yes.

Start Quench
This option will determine what event starts the quench cycle. The options are: On Recipe Opcode
(

QUENCH

Opcode), Input 1 – Input 31.


Quench Hold Event
This option will determine which event will hold the quench cycle. The list of possible values is: 0 – 15.


Advertising