Super Systems 9130 Series User Manual

Page 94

Advertising
background image

Series 9130 Operations Manual Rev -

93

Deviation and Temperature Band), A. + Dev, T. + Dev (Atmosphere + Deviation and Temperature +
Deviation), A. + Dev, T. – Dev (Atmosphere + Deviation and Temperature – Deviation), A. – Dev (Atmosphere
– Deviation), A. – Dev, T. Bnd (Atmosphere – Deviation and Temperature Band), A. – Dev, T. + Dev
(Atmosphere – Deviation and Temperature + Deviation), A. – Dev, T. – Dev (Atmosphere – Deviation and
Temperature – Deviation). There is also an option for Smart Temp and Smart Atm.
The band limit can be changed by the

SET_WAIT

opcode.

Temperature Value Column

Atmosphere Value Column

Option Value Column

DOW_INQ
N/A

N/A

Day

This opcode checks the real time clock for the day of the week. This is useful for performing operations on
a weekly basis on a specific day.
The Day is the day of the week, i.e. Sunday, Monday, Tuesday, Wednesday, Thursday, Friday, or Saturday.

EVT_IN
Temperature Setpoint N/A

Event

This opcode waits for an input event to be turned ON or OFF depending on the Event value selected.
If the Temperature Setpoint is specified, it is considered a set point and will be sent to the appropriate
controller.
The Temperature Setpoint ranges from -301 (Disable) – 30000.
The Event options are: Event 0 ON/OFF – Event 31 ON/OFF.

EVT_OUT
Temperature Setpoint N/A

Event

This opcode waits for an output event to be turned ON or OFF depending on the Event value selected.
If the Temperature Setpoint is specified, it is considered a set point and will be sent to the appropriate
controller.
The Temperature Setpoint ranges from -301 (Disable) – 30000.
The Event options are: Event 0 ON/OFF – Event 47 ON/OFF.

G_SOAK
N/A

Wait Limit

Soak Time

This is a guaranteed soak opcode. The temperature process value must be within the deviation band to
allow the soak timer to run. If the temperature process value goes out of the deviation band, then the soak
timer will stop and wait until the temperature process value comes back into the deviation band before
starting up again.
The Wait Limit is the wait time, in Hours: Minutes format, for the wait limit. The Hours range from 0 – 533,
and the Minutes range from 0 – 59.
The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –
166, and the Minutes range from 0 – 59.
The band limit can be changed by the

SET_WAIT

opcode.

GDELAY
N/A

N/A

Delay Time

This opcode is a guaranteed short delay. It guarantees on the temperature loop unless the load TCs are
enabled, in which case it guarantees against the load TC map for the specified number of seconds.
The Delay Time is from 1 – 500 seconds.

GHDELAY
N/A

N/A

Delay Time

This opcode is a guaranteed high short delay opcode. The temperature process value must be below the
high limit deviation band to allow the delay timer to run. If the temperature process value goes out of the
deviation band, then the delay timer will stop and wait until the temperature process value comes back into
the deviation band before starting up again.

Advertising