Series 9130 Operations Manual Rev -

95

Temperature Value Column

Atmosphere Value Column

Option Value Column

GLZDELAY
N/A

N/A

Delay Time

This is a guaranteed low short delay opcode for a zone. The temperature process value must be below the
deviation band to allow the delay timer to run. If the temperature process value goes out of the deviation
band, then the delay timer will stop and wait until the temperature process value comes back into the
deviation band before starting up again.
The Delay Time is from 1 – 500 seconds.

GLZSOAK
N/A

Wait Limit

Soak Time

This is a guaranteed soak low opcode for a zone. The temperature process value must be above the lower
limit deviation band to allow the soak timer to run. If the temperature process value goes out of the
deviation band, then the soak timer will stop and wait until the temperature process value comes back into
the deviation band before starting up again.
The Wait Limit is the wait time, in Hours: Minutes format, for the wait limit. The Hours range from 0 – 533,
and the Minutes range from 0 – 59.
The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –
166, and the Minutes range from 0 – 59.
The band limit can be changed by the

SET_WAIT

opcode.


GOSUB
N/A

N/A

Recipe Number

The go to subroutine opcode is used to call a program to run and then return to the calling program. This is
used to execute standard routines that can be used by many programs.

GOSUBs

can be stacked up to eight

(8) levels.
The Recipe Number is the recipe (program) to run. The range is 1 – 300.

GRAMP
Temperature Setpoint N/A

Time

This is a guaranteed ramp opcode. The process value must be within the deviation band to allow the ramp
timer to run. If the process value goes out of the deviation band, then the ramp timer will stop and wait
until the process value comes back into the deviation band before starting up again.
The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301
(disable) – 30000.
The Time is the total time for the program to reach the desired setpoint(s), in Hours:Minutes format. The
Hours range from 0 – 166, and the Minutes range from 0 – 59.
The band limit can be changed by the

SET_WAIT

opcode.

GTCINQDEL
Delay Time

T/C

Option

This is a guaranteed TC inquiry short delay opcode. It is used to verify that all active thermocouples are
within the set wait limits around the setpoint for the user defined time period.
The Delay Time is the time in seconds before checking the T/Cs. The range is 0 – 500.
The T/C is the Control T/C or Load T/C to use. The options are: Control T/C, T/C 1 – T/C 24.
The Option will allow the user to wait for the T/Cs to come within the set wait limits around the setpoint.
The options are: Wait, Wait Up, or Wait Down.