Data

The Process Variable (PV), Setpoint (SP), and Output (Out)
can be set up from this screen. Select the desired option
from the drop-down list to configure those settings.

Offset
The Offset field is the instrument’s register offset. The
range is 0 – 32767.

Instrument Register
The Instrument Register field is the register in the 9130
controller. The range is 0 – 32767.

Input Type
The Input Type field will determine what kind of type the

value will be. The options are: Integer, Big Endian, Big Endian Byte Swap, Little Endian, or Little Endian
Byte Swap.

Exponential
The Exponential field will determine if there is an exponent value. For “Integer” Input Types, exponents do
not apply, so this field is not modifiable. If the Input Type is not “Integer”, the options for the exponential
are: Yes or No.

Input Scalar
The Input Scalar field will determine the input scalar range. The range is -30 – 30.

Output Type
The Output Type will determine what kind of the output value will be. The options are: Integer, Big Endian,
Big Endian Byte Swap, Little Endian, or Little Endian Byte Swap.

Exponential
The Exponential field will determine if there is an exponent value. For “Integer” Input Types, exponents do
not apply, so this field is not modifiable. If the Input Type is not “Integer”, the options for the exponential
are: Yes or No.

Output Scalar
The Output Scalar field will determine the Output scalar range. The range is -30 – 30.

Tuning Assistant

The Tuning Assistant menu option will allow the user to
automatically generate the PID loop settings for the
control loops in the 9130 controller. Select the loop to
tune and click on the Edit button to auto tune that loop.

Note: The four buttons at the bottom of the screen: Use
UD (Under Damped), Use CD (Critically Damped), Use
OD (Over Damped), and Use PI will be inaccessible until
some PID settings are loaded into the PID settings list
above the buttons

. The Return button in the bottom right

of the screen will close down the screen. The user can
select the tuning option from the options at the top of the
screen. The choices are: Relay and Limited Relay.