Series 9130 Operations Manual Rev -

94

The Delay Time is from 1 – 500 seconds.
Temperature Value Column

Atmosphere Value Column

Option Value Column

GHSOAK
N/A

Wait Limit

Soak Time

This is a guaranteed soak high opcode. The temperature process value must be above the deviation band to
allow the soak timer to run. If the temperature process value goes out of the deviation band, then the soak
timer will stop and wait until the temperature process value comes back into the deviation band before
starting up again.
The Wait Limit is the wait time, in Hours: Minutes format, for the wait limit. The Hours range from 0 – 533,
and the Minutes range from 0 – 59.
The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –
166, and the Minutes range from 0 – 59.
The band limit can be changed by the

SET_WAIT

opcode.


GHZDELAY
N/A

N/A

Delay Time

This is a guaranteed high short delay opcode for a zone. The temperature process value must be below the
high limit deviation band to allow the delay timer to run. If the temperature process value goes out of the
deviation band, then the delay timer will stop and wait until the temperature process value comes back into
the deviation band before starting up again.
The Delay Time is from 1 – 500 seconds.

GHZSOAK
N/A

Wait Limit

Soak Time

This is a guaranteed soak high opcode for a zone. The temperature process value must be below the high
limit deviation band to allow the soak timer to run. If the temperature process value goes out of the
deviation band, then the soak timer will stop and wait until the temperature process value comes back into
the deviation band before starting up again.
The Wait Limit is the wait time, in Hours: Minutes format, for the wait limit. The Hours range from 0 – 533,
and the Minutes range from 0 – 59.
The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –
166, and the Minutes range from 0 – 59.
The band limit can be changed by the

SET_WAIT

opcode.


GLDELAY
N/A

N/A

Delay Time

This opcode is a guaranteed low short delay opcode. The temperature process value must be above the
lower limit deviation band to allow the delay timer to run. If the temperature process value goes out of the
deviation band, then the delay timer will stop and wait until the temperature process value comes back into
the deviation band before starting up again.
The Delay Time is from 1 – 500 seconds.

GLSOAK
N/A

Wait Limit

Soak Time

This is a guaranteed soak low opcode. The temperature process value must be above the lower limit
deviation band to allow the soak timer to run. If the temperature process value goes out of the deviation
band, then the soak timer will stop and wait until the temperature process value comes back into the
deviation band before starting up again.
The Wait Limit is the wait time, in Hours: Minutes format, for the wait limit. The Hours range from 0 – 533,
and the Minutes range from 0 – 59.
The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –
166, and the Minutes range from 0 – 59.
The band limit can be changed by the

SET_WAIT

opcode.