Series 9130 Operations Manual Rev -

63

This is the PID Switch Point field. This is used in conjunction with the PV Switching feature. See the

PV

Switching

section for more information. The range is –300 to 4000.

Setpoint Lower Limit
This is the lower limit of the setpoint. The range is –300 to 9999.

Setpoint Upper Limit
This is the upper limit for the setpoint. The range is –300 to 9999.

Event Run Program Setup

Event run program setup is used to start
a program that is stored in the 9130
vacuum controller (zero for buffered) or
by a defined event input.

*Program must be configured under the
menu option

Event Control


*Used to define an event input to initiate a
program start and to define which
program to start (zero starts the last
program run) from the contact closure.
The range of programs to run is 0 to 300.

*WARNING*
If a JUMP (to another program) is used in a previous program, the program that will run
would be the last program jumped to not the first program run.


If you stop a program in a GOSUB the program that will be run will be the GOSUB.

Zone/Load TC Setup

Configuration of any analog input device must be
completed under this menu item.

Load TC Enable
This value will manually toggle between on, on + alarms,
and off.
On – T/C Enabled
On + Alarms – T/C Enabled, Programmer alarm114
provided if out of band (Default wait limits)
Off – T/C not enabled

Control TC
This value allows the user to set the TC to be part of the
group of Load TCs that can hold the program if it is out of
band. The values are active or not active (shown as blank).

TC 1 – 24
This value allows the user to manually turn the T/C from active to not active, shown as blank, to be part of
the group of TCs that can hold the program if it’s out of band.