Super Systems 9130 Series User Manual

Page 68

Advertising
background image

Series 9130 Operations Manual Rev -

67

Cascade Inhibit

Note: This field is only applicable if the controller is in Cascade mode

. This will turn cascade control on or

off. When inhibit = enabled, the 9130 functions as a multi-loop controller with three control loops. The
options are: enabled or disabled.

PV Difference Cutback

Note: This field is only applicable if the controller is in Cascade Mode

. This is used with the Cascade Lower

Range EOPV and Cascade Upper Range EOPV to limit the absolute % output of the furnace loop. This will
turn the PV difference cutback feature on or off. The options are: enabled or disabled.

Cascade Lower Range EOPV

Note: This field is only applicable if the controller is in Cascade Mode

. This is the cascade lower range end

of PV difference. This is used with the PV Difference Cutback and Cascade Upper Range EOPV to limit the
absolute % output of the furnace loop. Between the lower range EPOV and the upper range EOPV, there is
a linear interpolation from 0 to the loop 2 output maximum (usually 100 %) that determines the maximum %
output for the furnace loop. The range is -300 to 10000.

Cascade Upper Range EOPV

Note: This field is only applicable if the controller is in Cascade Mode

. This is the cascade upper range end

of PV difference. This is used with the Cascade Lower Range EOPV and PV Difference Cutback to limit the
absolute % output of the furnace loop. Between the lower range EPOV and the upper range EOPV, there is
a linear interpolation from 0 to the loop 2 output maximum (usually 100 %) that determines the maximum %
output for the furnace loop. The range is -300 to 10000.

Default Hold Time
This value is the default holding time for the furnace. The range is 0 to 10000.

Deviation Alarm Delay
This value is the delay for the alarm if a deviation alarm is detected. The range is 0 to 10000.

Furnace Name
This is the name of the furnace.

PV1 Name
This is the name of process variable 1.

Clear events/end of recipe
This switch will allow the user to clear the events out at the end of a recipe. The options are either no or
yes.

Start Quench
This option will determine what starts the quench cycle. The options are: On Recipe Opcode (

QUENCH

Opcode), Input 1 – Input 31.

Quench Hold Event
This option will determine which event will hold the quench cycle. The options are: None, Input 1 – Input 14.

Quench/EVT Transfer Time Configuration
This option will allow the user to set what will trigger the transfer from the quench cycle. The options are:
Event 2 Active Time, or Event 1 Active to Event 2 Active.

Advertising