Series 9130 Operations Manual Rev -

68

PV Switch Action
This field will select the action for the PV switch. When an instrument in configured for PV switching, the
controller will use the “low” source when the PV signal is below the PV Switch Value; and it will use the
“high” source when the PV signal is above the PV Switch value. The list of options is:
None
PV Switch
TC Redundancy
Cascade Control

Default Wait Limits

The 9130 controller uses default wait limits in
conjunction with recipe programs. The wait limits are in
place to help make sure a recipe will not continue to the
next step until the temperature is within the specified
range. The wait limits are both plus and minus the value
of the setpoint specified in the recipe. You can define
specific wait limits per program that supersede the
defaults with the specific wait limit OP CODE per
program (SETWAIT).

Alarm Setup

The 9130 controller can be configured to use
three (3) different alarms, and a Thermocouple
Check. Each of the alarms consists of an alarm
setpoint, alarm type, alarm hysteresis, smart
alarm, ON delay time, 0 SP blocks alarm value,
Burnoff/Impedance inhibits alarm, Inhibit
source, and disable on open input. The alarms
come from the factory with a default
configuration dependent on the application but
also can be modified prior to shipment to your
facility or in the field by a supervisor.

Setpoint
This value is the setpoint for the alarm. Clicking
on this value will display an input box from

which the user can select a new value. The range is from –9999 to 9999.

Alarm Type
This value is the type of alarms used. Clicking on this value will display an input box with two (2) drop-down
lists from which the user can select a new value.
The values in the first (top) list box are:
PV 1 Value
PV 2 Value
N/A
Input 1 Value
Input 2 Value
Input 3 Value
PO1 Value
PO2 Value
N/A