ION 7500 / ION 7600 User’s Guide

Customizing Frameworks in Designer

Chapter 4 - Using ION Software

Page 113

Editing Existing Frameworks

If you are comfortable with the ION software and the meter’s configuration, you
can make changes to the existing frameworks to customize operation. Any edits
you make to the existing frameworks alter the device’s operation — be sure you
understand what effect your changes will have before proceeding.

Checking an Output Register’s “Owner”

Using Designer, right-click a module’s output register to view its linkages, referred
to as “owners”. A dialog box appears showing all of the inputs that are linked to
that output register. With this information you can determine what changes will
result to the framework by deleting the links to the parameter. Note that links to
inputs on other nodes are not shown in this dialog box.

C

AUTION

Viewing owners by right-clicking a module's output register will only show you module linkages on the
same node. Any links to modules on different nodes will not be shown. If links to modules on other nodes
may exist, always check the links at a module’s inputs.

Deleting the Link at a Module’s Input

You can also check the links at a module’s input. Using Designer, right-click on the
input symbol on a module to view a dialog box listing each of the inputs and the
output registers they are linked to. You can unlink inputs from within this dialog
box as well.

Replacing a Link

You do not need to unlink a module’s input before linking a different output
register to it. If you link an output register to an input that is already linked, the
existing link is overwritten.