Sag/Swell Module Configuration

ION 7500 / ION 7600 User’s Guide

Page 294

Power Availability Technical Note

4.

An auxiliary powered meter is used for applications that require a highly
accurate measurement of power system downtime.

Sag/Swell Module Configuration

Your meter’s power availability framework requires that the Sag/Swell module be
configured to the limits of your meter’s power supply specification. See the online
ION Programmer’s Reference for detailed information on the operation of the
Sag/Swell module.

Operating ranges of the ION 8000 Series meter are listed below:

The ANSI C84.1 1989 standard recommends a Swell limit of 106% for Range B
voltage levels, as well as a Sag limit of 88% for load voltages and 92% for the
service entrance.

Power
Supply

Operating Range

9S

36S

35S

3-Phase
blade
powered
meter

Option E

(120 – 277) ± 15%

(102 – 318.5) VLN rms)

(120 – 277) ± 15%

(102 – 318.5) VLN rms

120 – 480 ± 15%

(102V – 552) VLL rms

Option G

57.7 – 70VLN ± 15%

(49 – 80.5) VLN rms)

57 – 70VLN ± 15%

(49 – 80.5) VLN rms

N/A

Auxiliary
powered
meter

Option H

(High V)

(160 – 277) ± 20% (128 – 332.4) VLN rms

Option J

(Low V)

65 – 120 ± 20% (52 – 144) VLN rms