Interharmonic Voltage

ION 7500 / ION 7600 User’s Guide

Page 320

Power Quality: ION Meters and EN50160 Technical Note

Interharmonics Default Measurements

* This data is recorded weekly by Data Recorder 30.

Register Label

Source Module

Description

V1-Inthrm N*

Harmonics

Evaluation

number of valid intervals (voltage on phase 1 within +/- 15% of nominal)

V1-Inthrm N ivd*

number of invalid intervals

V1-Inthrm N1*

number of intervals in which one or more individual harmonics on phase 1 exceed their limits

V2-Inthrm N*

number of valid intervals (voltage on phase 2 within +/- 15% of nominal)

V2-Inthrm N ivd*

number of invalid intervals

V2-Inthrm N1*

number of intervals in which one or more individual harmonics on phase 2 exceed their limits

V3-Inthrm N*

number of valid intervals (voltage on phase 3 within +/- 15% of nominal)

V3-Inthrm N ivd*

number of invalid intervals

V3-Inthrm N1*

number of intervals in which one or more individual harmonics on phase 3 exceed their limits

PO V1-Inthrm N

Store

V1-Inthrm N of the previous Observation Period

PO V1-Inthrm N1

V1-Inthrm N1 of the previous Observation Period

PO V2-Inthrm N

V2-Inthrm N of the previous Observation Period

PO V2-Inthrm N1

V2-Inthrm N1 of the previous Observation Period

PO V3-Inthrm N

V3-Inthrm N of the previous Observation Period

PO V3-Inthrm N1

V3-Inthrm N1 of the previous Observation Period

V1-Inthrm N1/N

Arithmetic

N1/N ratio

V2-Inthrm N1/N

N1/N ratio

V3-Inthrm N1/N

N1/N ratio

PO V1-Ihrm N1/N

N1/N ratio of previous Observation Period

PO V2-Ihrm N1/N

N1/N ratio of previous Observation Period

PO V3-Ihrm N1/N

N1/N ratio of previous Observation Period