ION 7500 / ION 7600 User’s Guide

Electrical Specifications

Chapter 6 - Hardware Reference

Page 175

Current Inputs

Specification

5A Option

1A Option

Input Rating

5A, 10A, or 20A

1A, 2A, 5A, or 10A

Fault Capture

70A peak

17.5A peak

Maximum Voltage

600V RMS (CAT III IEC61010-1)

600V RMS (CAT III IEC61010-1)

Impedance

2 mΩ

15 mΩ

Burden

0.05 VA per phase (at 5A)

0.015 VA per phase (at 1A)

Dielectric Withstand

3250 VAC, 60Hz for 1 minute

3250 VAC, 60Hz for 1 minute

Overload

500A RMS for 1 second, non-

recurring

50A RMS for 1 second, non-

recurring