Using the Modbus RTU Protocol

ION 7500 / ION 7600 User’s Guide

Page 70

Chapter 3 - Default Meter Functionality

Modbus Slave Module Settings

The settings in the Modbus Slave module setup registers are shown in the tables
below. Refer to ION 7500 / ION 7600 Series meter Modicon Modbus Serial
Communications Protocol and ION/Modbus Register Map
document for additional
details on the Modbus implementation on the meter.

Modbus Slave Module #1

Modbus Slave Module #2

Setup Register

Setting

Setup Register

Setting

Format

unsigned 16-bit

Format

signed 32-bit

Base Address

40011

Base Address

40027

Scaling

YES

Scaling

YES

In Zero

0

In Zero

-214748364

In Full

6553

In Full

214748364

Out Zero

0

Out Zero

-2147483640

Out Full

65530

Out Full

2147483640

Modbus Slave Module #3

Modbus Slave Module #4

Setup Register

Setting

Setup Register

Setting

Format

signed 32-bit

Format

signed 32-bit MFP

Base Address

40059

Base Address

40089

Scaling

YES

Scaling

NO

In Zero

-214748364

In Full

214748364

Out Zero

-2147483640

Out Full

2147483640

Modbus Slave Modules #5 to #15 (EN50160 data)

Setup Register

Setting

Setup Register

Setting

Base Addresses

#5: 41000

Format

unsigned 16-bit

#6: 41016

Scaling

NO

#7: 41032

In Zero

-32767

#8: 41048

In Full

32767

#9: 41064

Out Zero

-32767

#10: 41080

Out Full

32767

#11: 41096

#12: 41112

#13: 41128

#14: 41144

#15: 41160