Flicker Default Measurements

* This data is recorded once a week by Data Recorder module 18.

Register Label

Source Module Type

Description

V1-Flck Pst

Flicker

Pst value for voltage on phase 1

V2-Flck Pst

Pst value for voltage on phase 2

V3-Flck Pst

Pst value for voltage on phase 3

V1-Flck Plt

Plt value for voltage on phase 1

V2-Flck Plt

Plt value for voltage on phase 2

V3-Flck Plt

Plt value for voltage on phase 3

V1-Flck N*

Signal Limit

Evaluation

number of valid intervals (voltage on phase 1 within +/- 15% of nominal and no dip >= 15%)

V1-Flck N invd*

number of invalid intervals

V1-Flck N1*

number of valid intervals in which Plt on phase 1 is greater than 1

V2-Flck N*

number of valid intervals (voltage on phase 2 within +/- 15% of nominal and no dip >= 15%)

V2-Flck N invd*

Signal Limit

Evaluation

number of invalid intervals

V2-Flck N1*

number of valid intervals in which Plt on phase 2 is greater than 1

V3-Flck N*

number of valid intervals (voltage on phase 3 within +/- 15% of nominal and no dip >= 15%)

V3-Flck N invd*

number of invalid intervals

V3-Flck N1*

number of valid intervals in which Plt on phase 3 is greater than 1

PO V1-Flck N

Store

V1-Flck N of the previous Observation Period

PO V1 Flck N1

V1-Flck N1 of the previous Observation Period

PO V2-Flck N

V2-Flck N of the previous Observation Period

PO V2 Flck N1

V2-Flck N1 of the previous Observation Period

PO V3-Flck N

V3-Flck N of the previous Observation Period

PO V3 Flck N1

V3-Flck N1 of the previous Observation Period

V1 Pst mn

Minimum

minimum Pst value for phase 1 over 1week (used for display purposes)

V1 Pst mx

Maximum

maximum Pst value for phase 1 over 1 week (used for display purposes)

V2 Pst mn

Minimum

minimum Pst value for phase 2 over 1week (used for display purposes)

V2 Pst mx

Maximum

maximum Pst value for phase 2 over 1 week (used for display purposes)

V3 Pst mn

Minimum

minimum Pst value for phase 3 over 1week (used for display purposes)

V3 Pst mx

Maximum

maximum Pst value for phase 3 over 1 week (used for display purposes)

V1-Flck N1/N

Arithmetic

N1/N ratio

V2-Flck N1/N

Arithmetic

N1/N ratio

V3-Flck N1/N

Arithmetic

N1/N ratio

PO V1-Flck N1/N

Arithmetic

N1/N ratio of the previous Observation Period

PO V2-Flck N1/N

Arithmetic

N1/N ratio of the previous Observation Period

PO V3-Flck N1/N

Arithmetic

N1/N ratio of the previous Observation Period