Multi-Tech Systems 7500 User Manual

Page 305

Advertising
background image

ION 7500 / ION 7600 User’s Guide

Magnitude of Voltage Supply

Power Quality: ION Meters and EN50160 Technical Note

Page 305

Voltage Magnitude Default Measurements

* This data is recorded once a week by Data Recorder module 17.

Register

Source Module Type

Description

V1-Mag N*

Signal Limit Evaluation

number of valid intervals (voltage on phase 1 within +/- 15% of nominal)

V1-Mag N invld*

number of invalid intervals

V1-Mag N1*

number of valid intervals in which the voltage deviates from nominal by more than +/-10%

V2-Mag N*

number of valid intervals (voltage on phase 2 within +/- 15% of nominal)

V2-Mag N invld*

number of invalid intervals

V2-Mag N1*

number of valid intervals in which the voltage deviates from nominal by more than +/- 10%

V3-Mag N*

number of valid intervals (voltage on phase 3 within +/- 15% of nominal)

V3-Mag N invld*

number of invalid intervals

V3-Mag N1*

number of valid intervals in which the voltage deviates from nominal by more than +/- 10%

PO V1-Mag N

Store

V1-Mag N of the previous Observation Period

PO V1-Mag N1

V1-Mag N1 of the previous Observation Period

PO V2-Mag N

V2-Mag N of the previous Observation Period

PO V2-Mag N1

V2-Mag N1 of the previous Observation Period

PO V3-Mag N

V3-Mag N of the previous Observation Period

PO V3-Mag N1

V3-Mag N1 of the previous Observation Period

V1 mean

Sliding Window Demand

average voltage on phase 1 over 10m (used for display purposes)

V1 mean mn

Minimum

minimum of average voltage V1 (V1 mean) over 1 week (used for display purposes)

V1 mean mx

Maximum

maximum of average voltage V1 (V1 mean) over 1 week (used for display purposes)

V2 mean

Sliding Window Demand

average voltage on phase 2 over 10m (used for display purposes)

V2 mean mn

Minimum

minimum of average voltage V2 (V2 mean) over 1 week (used for display purposes)

V2 mean mx

Maximum

maximum of average voltage V2 (V2 mean) over 1 week (used for display purposes)

V3 mean

Sliding Window Demand

average voltage on phase 3 over 10m (used for display purposes)

V3 mean mn

Minimum

minimum of average voltage V3 (V3 mean) over 1 week (used for display purposes)

V3 mean mx

Maximum

maximum of average voltage V3 (V3 mean) over 1 week (used for display purposes)

V1-Mag N1/N

Arithmetic

N1/N ratio

V2-Mag N1/N

N1/N ratio

V3-Mag N1/N

N1/N ratio

PO V1-Mag N1/N

N1/N ratio of the previous Observation Period

PO V2-Mag N1/N

N1/N ratio of the previous Observation Period

PO V3-Mag N1/N

N1/N ratio of the previous Observation Period

Advertising
This manual is related to the following products: