ION 7500 / ION 7600 User’s Guide

Analog Input Module

Digital and Analog I/O Technical Note

Page 225

N

OTE

Once you have set the

Port

setup register to the appropriate analog input port on the meter, link the

ScaledValu

output register to another software module or framework for analysis.

Detailed Operation

The following example illustrates the Analog Input module with an input coming
from 50% of the highest possible input value. The Analog Input module takes the
input value and calculates what it corresponds to on the new scale, which is
defined by the Zero Scale and Full Scale registers. In this case, 50% on the new scale
is a value of 75. This value is written into the ScaledValu output register.

Setup Register

Description

Zero Scale

Defines the value that appears in the

ScaledValu

output register when the

lowest value from the hardware port is applied

Full Scale

Defines the value that appears in the

ScaledValu

output register when the

highest value from the hardware port is applied

Port

Defines the hardware port that provides the signal