I/o specifications, Digital inputs, Rear view of meter – Multi-Tech Systems 7500 User Manual

Page 169

Advertising
background image

ION 7500 / ION 7600 User’s Guide

I/O Specifications

Chapter 6 - Hardware Reference

Page 169

I/O Specifications

Digital Inputs

AI4

AO4

AI3

A03

AI2

A02

AI1

AO1

Rear View of Meter

Analog connections from
external transducers
0 to 20 mA or 0 -1 mA

Analog Connections to
analog transducers
0 to 20mA: 500 Ohm load Max
-1 to 1mA: 10k Ohm load Max

Digital connections from
external relays or pulse counter
50 VDC Max

External Dry Contacts
(polarity for SSR
contacts shown)

AWG 12 to 14 (3.3 to 2.1 mm ) recommended; wire sizes will vary depending on application

2

DI1

DI2

DI3

DI4

DI5

DI6

DI7

DI8

DICOM

AI1

+

-

AO1

OUTCOM

I/O

CARD

Standard I/O

Locations

Specification

Standard I/O (S1 to S8)

Expansion Card I/O
(D11 to D18)

Min Pulse Width

1 millisecond

20 milliseconds

Max Pulse Rate

20 Hz

25 Hz

Scan Time

1 millisecond for all inputs (min)

20 milliseconds for all inputs (min)

Isolation to Ground

300 VDC for 10 seconds, 60 Hz

300 VDC for 10 seconds, 60 Hz

Max Voltage

130 VDC (continuous)

50 VDC (continuous)

Timestamp Accuracy

1 millisecond

2 milliseconds

Connection Type

Captured-wire

Wire Type

AWG 14 to AWG 12

Advertising
This manual is related to the following products: