Using Telnet

ION 7500 / ION 7600 User’s Guide

Page 332

Telnet and HyperTerminal Access Technical Note

Using Telnet

N

OTE

Use Telnet if your meter has Ethernet capabilities. Use HyperTerminal if your meter is connected serially
or through a modem to your workstation.

A Telnet session lets you:

access certain Ethernet communications module settings

view Ethernet statistics

access certain Power Meter module settings

access certain Factory module settings

clear the front panel event log display on the ION 8000 Series meters

configure Factory module setup registers for Current Probe Input applications

To connect to the meter:

1.

Choose

Run...

from the Windows

Start

menu and type the word telnet. Press

Enter.

2.

To connect to the meter choose

Connect

from the main menu and select

Remote

System...

3.

Type in the meter IP address in the Host Name box.

N

OTE

The IP address must match the IP address setup register in the meter Ethernet communications module.

4.

Leave the Port value and the TermType setting as the defaults. Press Enter. The
Login screen appears.

5.

Type the meter type (such as 7500) as the Login depending on the type of meter
you have. Press Enter.

6.

Type the meter password (“0” by default). Press Enter.

N

OTE

If ten incorrect passwords are entered in succession the Telnet access locks-out for 24 hours or until the
security features are disabled with the front panel of the meter.

7.

Type “?” for meter Help screen. Press Enter. A list of menu options appears.