Multi-Tech Systems 7500 User Manual

Page 350

Advertising
background image

Clock Module Settings

ION 7500 / ION 7600 User’s Guide

Page 350

Time Synchronization & Timekeeping Technical Note

Time Zone Adjustment:

The TZ Offset register specifies the time zone applicable to the area in which the
meter resides. It is obtained by adding or subtracting the appropriate number of
hours and minutes (hh:mm) from UTC time.

Daylight Savings Time Adjustment:

The DST Offset register holds the Daylight Savings Time offset applicable to the
meter’s location. The DST Offset is the amount of time in hours and minutes
(hh:mm) that the clock is adjusted when Daylight Savings Time begins.

N

OTE

The setup registers, DST Offset and TZ Offset have no affect on the information recorded by a meter’s
data and event recorders. These recorders always use UTC as their timestamped reference.

Communications Port Used for Synchronization:

The Time Sync Source setup register specifies which communications port receives
time synchronization signals. Only signals received on the selected port are used
for time synchronization; all other time synchronization signals are ignored.
Signals can be received on the following ports:

N

OTE

GPS Time Synchronization cannot be used with the Ethernet port, since time synchronization accuracy
cannot be guaranteed--there is no way to determine when a packet will arrive over the Ethernet.

Time synchronization can be achieved using ION and DNP 3.0 protocols. GPS time
synchronization uses special protocols defined for the type of GPS receiver you are
using. The following table summarizes the time synchronization sources:

1

Note that ION time synchronization only uses the

UTC

setting; the

LOCAL

setting cannot be used.

COM1 RS-232/RS-485 port

COM3 optical port

COM2 RS-485 port or optional internal
modem

10Base-T Ethernet port

Source of Synchronization used
for the Time Sync Source Register

Protocol Register in the
Communications Module

Time Sync Type Register in
the Clock Module

Clock Source Register in
the Clock Module

ION

ION

UTC1

LINEFREQ

,

INTERNAL

DNP

DNP

UTC

/

LOCAL

LINEFREQ

,

INTERNAL

Arbiter 1092

GPS

:

ARBITER

GPS

:

ARBITER

-

VORNE

UTC

/

LOCAL

COMM

True Time XL-DC

GPS

:

TRUETIME

/

DATUM

UTC

/

LOCAL

COMM

Datum Exac Time

GPS

:

TRUETIME

/

DATUM

UTC

/

LOCAL

COMM

Clark GPS-200-ASCII

GPS

:

TRUETIME

/

DATUM

UTC

/

LOCAL

COMM

Advertising