Magnitude of voltage supply – Multi-Tech Systems 7500 User Manual

Page 304

Advertising
background image

Magnitude of Voltage Supply

ION 7500 / ION 7600 User’s Guide

Page 304

Power Quality: ION Meters and EN50160 Technical Note

Magnitude of Voltage Supply

Each measurement is the mean of RMS voltage for each phase over fixed 10-minute
intervals. The nominal value is defined by the Sag/Swell module’s Nom Volts setup
register.

N

OTE

Nom Volts

is typically setup when the meter is placed into service; if

Nom Volts

has not been set, enter a

value for your system’s nominal voltage. This value will be used in all EN50160 compliance calculations.

Observation period of one week with fixed steps of 10 minutes.

N = number of 10-minute intervals in which the supply voltage is within ±15% of
nominal.

N

1

= number of intervals in which the supply voltage differs more than 10%

from nominal and supply voltage is within ±15% of nominal.

Supply voltage complies with the standard if N

1

/N <= 5% during the observation

period (1 week by default).

EN 50160 data (current observation period): The meter generates the N and N

1

counts for each phase as described above. These counters are reset at the beginning
of the next observation period.

EN 50160 data (previous observation period): The meter stores the N and N

1

counter values at the end of each observation period before these counters are
reset. These 6 registers are also stored in a data recorder for each observation
period.

Events: The meter creates a message in the Event log every time the N

1

counter for

each phase increases.

Parameter data: The meter can be enabled to record the 10-minute mean, ½ cycle
minimum and ½ cycle maximum values of supply voltage for each phase into a
data recorder every 10 minutes.